0
چهارشنبه 21 آذر 1397
سبد خرید ( 0 )
responsive carousel
QUINT-PS/ 1AC/24DC/10 - 2866763
مدل: 2866763
شرح: منبع تغذیه پاور 10 آمپر
 

Dimensions

Width 60 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 63 mm

Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height 5000 m

Back to top

Input data

Nominal input voltage range 100 V AC ... 240 V AC
  110 V DC ... 250 V DC
Input voltage range 85 V AC ... 264 V AC
  90 V DC ... 350 V DC (UL 508: ≤ 300 V DC)
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Discharge current to PE < 3.5 mA
Current consumption 2.2 A (120 V AC)
  1.3 A (230 V AC)
  2.5 A (110 V DC)
  1.2 A (220 V DC)
Nominal power consumption 302 VA
Inrush surge current < 15 A
Mains buffering > 36 ms (120 V AC)
  > 36 ms (230 V AC)
Input fuse 10 A (slow-blow, internal)
Choice of suitable circuit breakers 10 A ... 20 A (AC: Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester

Back to top

Output data

Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25 °C ... 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost) 15 A (-25°C ... 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance max. 35 V DC
Protection against surge voltage on the output < 35 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
  < 2 % (change in load, dynamic 10 % ... 90 %)
  < 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Output power 240 W
Typical response time < 0.15 s
Maximum power dissipation in no-load condition 9.1 W
Power loss nominal load max. 22 W

Back to top

General

Net weight 1.1 kg
Efficiency > 92.5 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
  2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
  2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Protection class I
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 940000 h (25 °C)
  > 530000 h (40 °C)
  > 230000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom

Back to top

Connection data, input

Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3

Back to top

Connection data, output

Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3

Back to top

Connection data for signaling

Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Screw thread M3

Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011 (EN 55022)
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CSA
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-4-5
Signal 1 kV (Test Level 2 - asymmetrical)
Standards/regulations EN 61000-6-3
  EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Equipment safety BG (design tested)
Standard - Approval for medical use IEC 60601-1, 2 x MOOP
Shipbuilding approval DNV GL (EMC B), ABS, LR, RINA, NK, BV
UL approvals UL Listed UL 508
  UL/C-UL Recognized UL 60950-1
  UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
DeviceNet approval DeviceNet™ Power Supply Conformance Tested
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
  15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to mains voltage dips SEMI F47-0706 Compliance Certificate
Information technology equipment - safety (CB scheme) IEC 60950-1 (2nd Edition)
Rail applications EN 50121-4
Overvoltage category (EN 62477-1) III

Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
  For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”