VAL-MS-T1/T2 335/12.5/3+1 - 2800184
مدل: 2800184
شرح: برقگیر- ارستر ترکیبی B+C
 

Dimensions

Height 89.8 mm
Width 71.2 mm
Depth 77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch 4 Div.

Back to top

Ambient conditions

Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

Back to top

General

IEC test classification I / II
  T1 / T2
  T1
  I
EN type T1 / T2
  T1
IEC power supply system TT
  TN-S
Mode of protection L-N
  L-PE
  N-PE
Mounting type DIN rail: 35 mm
Color jet black RAL 9005
Housing material PA 6.6
  PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, two-section, divisible
Number of positions 4
Surge protection fault message optical

Back to top

Protective circuit

Nominal voltage UN 240/415 V AC (TN-S)
  240/415 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage U(L-N) 335 V AC
Maximum continuous operating voltage UC (L-PE) 335 V AC
Maximum continuous voltage UC (N-PE) 264 V AC
Rated load current IL 80 A
Residual current IPE ≤ 5 µA
Standby power consumption PC ≤ 810 mVA
Nominal discharge current In (8/20) µs (L-N) 12.5 kA
Nominal discharge current In (8/20) µs (L-PE) 12.5 kA
Nominal discharge current In (8/20) µs (N-PE) 50 kA
Maximum discharge current Imax (8/20) µs 50 kA
Impulse discharge current (10/350) µs (L-N), charge 6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy 39 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp 12.5 kA
Impulse discharge current (10/350) µs (L-PE), charge 6.25 As
Impulse discharge current (10/350) µs (L-PE), specific energy 39 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp 12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge 25 As
Impulse discharge current (10/350) µs (N-PE), specific energy 625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp 50 kA
Total discharge current Itotal (8/20) µs 50 kA
Total discharge current Itotal (10/350) µs 50 kA
Follow current interrupt rating Ifi (N-PE) 100 A
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up (L-N) ≤ 1.2 kV
  ≤ 1.6 kV (30 kA - 8/20 µs)
Voltage protection level Up (L-PE) ≤ 2 kV
Voltage protection level Up (N-PE) ≤ 1.7 kV
Residual voltage Ures (L-N) ≤ 1.2 kV (at In)
  ≤ 1.1 kV (at 10 kA)
  ≤ 1 kV (at 5 kA)
  ≤ 0.9 kV (at 3 kA)
Residual voltage Ures (L-PE) ≤ 2 kV (at In)
  ≤ 1.5 kV (at 10 kA)
  ≤ 1.2 kV (at 5 kA)
  ≤ 1.1 kV (at 3 kA)
Residual voltage Ures (N-PE) ≤ 0.6 kV (at In)
  ≤ 0.5 kV (at 10 kA)
  ≤ 0.5 kV (at 5 kA)
  ≤ 0.4 kV (at 3 kA)
TOV behavior at UT (L-N) 415 V AC (5 s / withstand mode)
  457 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / withstand mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Max. backup fuse with V-type through wiring 80 A (gG - 16 mm²)
Max. backup fuse with branch wiring 160 A (gG)

Back to top

Connection data

Connection method Screw connection
Screw thread M5
Tightening torque 3 Nm (1,5 mm² ... 16 mm²)
  4.5 Nm (25 mm² ... 35 mm²)
Stripping length 16 mm
Conductor cross section flexible 1.5 mm² ... 25 mm²
Conductor cross section solid 1.5 mm² ... 35 mm²
Conductor cross section AWG 15 ... 2
Connection method Fork-type cable lug
Conductor cross section flexible 1.5 mm² ... 16 mm²

Back to top

UL specifications

SPD Type 4CA
Maximum continuous operating voltage MCOV (L-L) 670 V AC
Maximum continuous operating voltage MCOV (L-N) 335 V AC
Maximum continuous operating voltage MCOV (L-G) 335 V AC
Maximum continuous operating voltage MCOV (N-G) 264 V AC
Nom. voltage 415/240 V AC
Mode of protection L-L
  L-N
  L-G
  N-G
Power distribution system 3Y
Nominal frequency 50/60 Hz
Measured limiting voltage MLV (L-L) 3570 V
Measured limiting voltage MLV (L-N) 2630 V
Measured limiting voltage MLV (L-G) 3600 V
Measured limiting voltage MLV (N-G) 2600 V
Nominal discharge current In (L-L) 20 kA
Nominal discharge current In (L-N) 20 kA
Nominal discharge current In (L-G) 20 kA
Nominal discharge current In (N-G) 20 kA

Back to top

UL connection data

Conductor cross section AWG 10 ... 2
Tightening torque 30 lbf-in.

Back to top

Standards and Regulations

Standards/regulations IEC 61643-11 2011
  EN 61643-11 2012

Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
  No hazardous substances above threshold values