PSR-PC40-2NO-1DO-24DC-SC - 2700588
مدل: 2700588
شرح: رله حفاظتی - ایمنی SILE 3 فونیکس کنتاکت
 

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area

Back to top

 

Dimensions

Width 12.5 mm
Height 112.2 mm
Depth 114.5 mm

Back to top

 

Ambient conditions

Ambient temperature (operation) -40 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Maximum altitude ≤ 2000 m (Above sea level)

Back to top

 

Power supply

Rated control circuit supply voltage US 24 V DC -15 % / +10 %
  20.4 V DC ... 26.4 V DC
Rated control supply current IS typ. 75 mA
Power consumption at US typ. 1.8 W
Inrush current 400 mA (Δt < 100 µs at Us)
Filter time max. 2 ms (at A1-A2; test pulse width)
  ≥ 100 ms (at A1-A2; test pulse rate)
Protective circuit Surge protection Suppressor diode
  Protection against polarity reversal for rated control circuit supply voltage

Back to top

 

Digital inputs

Inrush current < 10 mA (Y1-Y2)
Current consumption < 5 mA (Y1-Y2)
Voltage at input/start and feedback circuit 24 V DC -15 % / +10 % (Y1-Y2)
Max. permissible overall conductor resistance 150 Ω (Y1-Y2)

Back to top

 

Relay outputs: enabling current path

Output name Enabling current path
Output description safety-related N/O contacts
Number of outputs 2 (undelayed)
Contact type 2 enabling current paths
Contact material AgSnO2
Switching voltage min. 12 V AC/DC
  max. 250 V AC/DC
Limiting continuous current 6 A (observe derating)
Inrush current min. 3 mA
  max. 6 A
Sq. Total current 60 A2 (observe derating)
Switching capacity min. 60 mW
Switching frequency max. 0.5 Hz
Mechanical service life 10x 106 cycles
Output fuse 6 A gL/gG (N/O contact)
  4 A gL/gG (for low-demand applications)

Back to top

 

Alarm outputs

Output description non-safety-related
Number of outputs 1 (digital, PNP)
Voltage 22 V DC (Us - 2 V)
Current max. 100 mA
Maximum inrush current 500 mA (Δt = 1 ms at Us)
Short-circuit protection no
Output fuse 150 mA fast blow

Back to top

 

Times

Typical pickup time at US < 200 ms (when controlled via A1, automatic start)
Typical release time at US < 35 ms (when controlled via A1)
Recovery time 500 ms

Back to top

 

General

Relay type Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205)
Nominal operating mode 100% operating factor
Net weight 177.4 g
Mounting position vertical, horizontal, with front of module upward
Mounting type DIN rail mounting
Assembly instructions See derating curve
Degree of protection IP20
Min. degree of protection of inst. location IP54
Housing material PBT
Housing color yellow
Operating voltage display 1 x yellow LED
Status display 2 x green LEDs
Indication 1 x red LED

Back to top

 

Connection data

Connection method Screw connection
pluggable Yes
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3

Back to top

 

Safety-related characteristic data

Stop category 0
Designation IEC 61508 - High demand
Safety Integrity Level (SIL) 3 (< 15% of the overall SIL)
Designation IEC 61508 - Low demand
Safety Integrity Level (SIL) 3 (< 15% of the overall SIL)
Designation EN 50156
Safety Integrity Level (SIL) 3

Back to top

 

Standards and Regulations

Designation Air clearances and creepage distances between the power circuits
Standards/regulations DIN EN 50178, EN 60079-15
Rated insulation voltage 250 V AC
Rated surge voltage/insulation Safe isolation, 6 kV reinforced insulation from control circuit, start circuit, signal output to the enabling current paths, 4 kV/basic insulation between the enabling current paths and between all current paths and housing
Degree of pollution 2
Overvoltage category III
Shock 15g
Vibration (operation) 2g
Conformance CE-compliant
UL, USA/Canada cULus
  Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X
  Class I, Div. 2, Groups A, B, C, D
GL C, EMC2
Environmental simulation test ISA-S71.04 (G3)

Back to top

 

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
  For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”