0
چهارشنبه 21 آذر 1397
سبد خرید ( 0 )
responsive carousel
MACX PL-EX-T-UIREL-UP - 2904910
مدل: 2904910
شرح: رله حفاظتی
 

Dimensions

Width 35 mm
Height 99 mm
Depth 114.5 mm

Back to top

Ambient conditions

Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) typ. 5 % ... 95 % (non-condensing)
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Shock 15g, according to IEC 60068-2-27
Vibration (operation) 5g, accordance to IEC 60068-2-6

Back to top

Input data

Sensor types (RTD) that can be used Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range -200 °C ... 850 °C
Input signal range 0 Ω ... 50 kΩ
Potentiometer resistance range 0 Ω ... 50 kΩ
Input signal range -1000 mV ... 1000 mV

Back to top

Output data

Configurable/programmable Yes
Current output signal 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL)
Max. current output signal 22 mA
Load/output load current output ≤ 600 Ω (20 mA)
Behavior in the event of a sensor error according to NE 43 or freely configurable
Output name Relay output
Output description 1 SIL/PL
Configurable/programmable Yes
Contact type 2 PDT
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 250 V AC (250 V DC)
Maximum inrush current 2 A (250 V AC)
  2 A (28 V DC)
  0.2 A (120 V DC)
Mechanical service life 1x 105 cycles

Back to top

Power supply

Supply voltage range 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Typical current consumption < 100 mA (24 V DC)
Power consumption < 2.4 W

Back to top

Connection data

Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 7 mm
Screw thread M3
Connection method Screw connection
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Back to top

General

Maximum transmission error 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA)
Maximum temperature coefficient 0.01 %/K
Step response (0–99%) typ. 1000 ms (With SIL)
  typ. 700 ms (Without SIL)
Status display Green LED (supply voltage, PWR)
  Red LED, flashing (line, sensor error, ERR)
  Red LED (module error, ERR)
  Yellow LED (switching output)
Flammability rating according to UL 94 V0
Degree of pollution 2
Overvoltage category II
Electromagnetic compatibility Conformance with EMC directive
Housing material PA 6.6-FR
Color yellow
Designation Input/output/power supply
Electrical isolation 2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/switching output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output/supply
Electrical isolation 300 Vrms (Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
Conformance CE-compliant
ATEX  II (1) G [Ex ia Ga] IIC
   II (1) D [Ex ia Da] IIIC
   II 3 G Ex nA nC ic IIC T4 Gc X
IECEx [Ex ia Ga] IIC
  [Ex ia Da] IIIC
  Ex nA nC ic IIC T4 Gc X
UL, USA/Canada UL 508 Listed
SIL 2

Back to top

Safety data

Max. internal inductance Li negligible
Max. internal capacitance Ci 44 nF
Max. output voltage Uo 6 V
Max. output current Io 7.4 mA
Max. output power Po 11 mW
Group IIC
Max. external inductivity Lo 100 mH
Max. external capacity Co 1.3 µF
Group IIC
Max. external inductivity Lo 10 mH
Max. external capacity Co 1.7 µF
Group IIC
Max. external inductivity Lo 1 mH
Max. external capacity Co 2.6 µF
Group IIC
Max. external inductivity Lo 0 mH
Max. external capacity Co 10 µF
Group IIB
Max. external inductivity Lo 100 mH
Max. external capacity Co 6.8 µF
Group IIB
Max. external inductivity Lo 10 mH
Max. external capacity Co 9.2 µF
Safety-related maximum voltage Um 253 V AC/DC

Back to top

EMC data

Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 2 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 2 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 2 %

Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
  EN 61000-4-4
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Electrical isolation 4-way, between input/output/power supply/switching output
Flammability rating according to UL 94 V0
Shock 15g, according to IEC 60068-2-27
Vibration (operation) 5g, accordance to IEC 60068-2-6
Conformance CE-compliant
ATEX  II (1) G [Ex ia Ga] IIC
   II (1) D [Ex ia Da] IIIC
   II 3 G Ex nA nC ic IIC T4 Gc X
IECEx [Ex ia Ga] IIC
  [Ex ia Da] IIIC
  Ex nA nC ic IIC T4 Gc X
UL, USA/Canada UL 508 Listed
Group IIC
  IIC
  IIC
  IIC
  IIB
  IIB

Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
  For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”