0
چهارشنبه 21 آذر 1397
سبد خرید ( 0 )
responsive carousel
MACX PL-T-UIREL-UP -2904901
مدل: 2904901
شرح: رله حفاظتی
 

Dimensions

Width 35 mm
Height 99 mm
Depth 114.5 mm

Back to top

Ambient conditions

Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) typ. 5 % ... 95 % (non-condensing)
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Back to top

Input data

Sensor types (RTD) that can be used Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range -200 °C ... 850 °C
Input signal range 0 Ω ... 50 kΩ
Potentiometer resistance range 0 Ω ... 50 kΩ
Input signal range -1000 mV ... 1000 mV

Back to top

Output data

Configurable/programmable Yes
Current output signal 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL)
Max. current output signal 22 mA
Load/output load current output ≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor error according to NE 43 or freely configurable
Output name Relay output
Output description 1 SIL/PL
Configurable/programmable Yes
Contact type 2 PDT
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 250 V AC (250 V DC)
Maximum inrush current 2 A (250 V AC)
  2 A (28 V DC)
  0.2 A (120 V DC)

Back to top

Power supply

Supply voltage range 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Power consumption < 2.4 W

Back to top

Connection data

Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Screw thread M3
Connection method Screw connection

Back to top

General

Maximum transmission error 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA)
Maximum temperature coefficient 0.01 %/K
Flammability rating according to UL 94 V0
Degree of pollution 2
Overvoltage category II
Electromagnetic compatibility Conformance with EMC directive
Housing material PA 6.6-FR
Color yellow
Designation Input/output/power supply
Electrical isolation 300 Vrms (Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
  2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/switching output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Conformance CE-compliant
ATEX  II 3 G Ex nA nC ic IIC T4 Gc X
IECEx Ex nA nC ic IIC T4 Gc X
UL, USA/Canada UL 508 Listed
  Class I, Div. 2, Groups A, B, C, D T6
  Class I, Zone 2, Group IIC T6
SIL 2

Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Electrical isolation 4-way, between input/output/power supply/switching output
Flammability rating according to UL 94 V0
Conformance CE-compliant
ATEX  II 3 G Ex nA nC ic IIC T4 Gc X
IECEx Ex nA nC ic IIC T4 Gc X
UL, USA/Canada UL 508 Listed
  Class I, Div. 2, Groups A, B, C, D T6
  Class I, Zone 2, Group IIC T6

Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
  For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”