بریرEX جهت ورودی آنالوگ فونیکس کنتاکت

Ex i repeater power supply and input signal conditioner, HART. Transmits supplied or active 0/4 – 20 mA signals from the hazardous area to a load (active or passive) in the safe area. 3-way electrical isolation; SIL 2 according to IEC 61508, with screw connection

توضیحات

Power/input isolating amplifier – MACX MCR-EX-SL-RPSSI-I – 2865340
Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals from the Ex area to a load (active or passive) in the safe area. 3-way electrical isolation, SIL 2 in accordance with IEC 61508, with screw connection
Dimensions
Width 12.5 mm
Height 112.5 mm
Depth 113.7 mm
114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)
Back to top
Ambient conditions
Ambient temperature (operation) -20 °C … 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C … 80 °C
Permissible humidity (operation) 10 % … 95 % (non-condensing)
Degree of protection IP20 (not assessed by UL)
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Altitude ≤ 2000 m (For use at altitudes ≥2000 m above sea level, see data sheet.)
Ambient temperature (operation) -20 °C … 60 °C
Rated insulation voltage 375 VPP (Power supply, input / output)
Altitude ≤ 3000 m
Ambient temperature (operation) -20 °C … 54 °C
Rated insulation voltage 190 V AC (Power supply, input / output)
110 V DC (Power supply, input / output)
Altitude ≤ 4000 m
Ambient temperature (operation) -20 °C … 48 °C
Rated insulation voltage 60 V AC/DC (Power supply, input / output)
Altitude ≤ 5000 m
Ambient temperature (operation) -20 °C … 42 °C
Rated insulation voltage 60 V AC/DC (Power supply, input / output)
Altitude > 2000 m
≤ 3000 m
> 3000 m
≤ 5000 m
Back to top
Input data
Signal input Active current input, intrinsically safe
Current input signal 4 mA … 20 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Underload/overload signal range 0 mA … 24 mA (Extended transmission range for diagnostics)
Polarization and surge protection Yes
Signal input Passive current input, intrinsically safe
Current input signal 0 mA … 20 mA
4 mA … 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation) Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics) Back to top Output data Signal output Current output (active and passive) Current output signal 4 mA ... 20 mA (active) 4 mA ... 20 mA (14 ... 26 V ext. source voltage) Transmission Behavior 1:1 to input signal Load/output load current output < 1000 Ω (20 mA) < 825 Ω (24 mA) Output ripple < 20 mVrms Output behavior in the event of an error 0 mA (Cable break in the input) ≥ 22.5 mA (Cable short-circuit in the input) Signal output Current output (active and passive) Current output signal 0 mA ... 20 mA (active) 4 mA ... 20 mA (active) 0 mA ... 20 mA (14 ... 26 V ext. source voltage) 4 mA ... 20 mA (14 ... 26 V ext. source voltage) Transmission Behavior 1:1 to input signal Load/output load current output < 1000 Ω (20 mA) < 825 Ω (24 mA) Output ripple < 20 mVrms Output behavior in the event of an error 0 mA (Cable break in the input) 0 mA (Cable short-circuit in the input) Back to top Power supply Designation Repeater power supply operation Nominal supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) Max. current consumption < 76 mA (24 V DC / 20 mA / 1000 Ω) Power dissipation < 1.1 W (24 V DC / 20 mA / 1000 Ω) Power consumption < 1.8 W (20 mA / 1000 Ω) Designation Signal conditioner operation Nominal supply voltage range 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) Max. current consumption < 44 mA (24 V DC / 20 mA / 1000 Ω) Power dissipation < 0.75 W (24 V DC / 20 mA / 1000 Ω)