مبدل پتانسیومتر به سیگنال 2902016

مبدل پتانسیومتر به سیگنال آنالوگ استاندارد

100Ω – 100KΩ

توضیحات

Resistance/potiposition transducer – MINI MCR-2-POT-UI

2902016

Configurable potiposition transducer with plug-in connection technology for connecting potentiometers from 0 Ω … 100 Ω to 0 kΩ … 100 kΩ. Configurable via DIP switch or software. Screw connection technology, standard configuration

 

No. of channels 1
Rated insulation voltage 300 V (effective)
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Test voltage, input/output/supply 3 kV (50 Hz, 1 min.)
Protective circuit Transient protection
Step response (0–99%) < 60 ms
Maximum temperature coefficient 0.01 %/K
Temperature coefficient, typical 0.01 %/K
Maximum transmission error < 0.1 % (R < 240 Ω = < 0,2 %)
Supply
Nominal supply voltage 24 V DC
Supply voltage range 9.6 V DC … 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Item No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption 33 mA (24 V DC)
68 mA (12 V DC)
Power consumption ≤ 850 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)

Potentiometer
Potentiometer resistance range 100 Ω … 100 kΩ
Signal
Number of inputs 1

Signal: Voltage/current
Output name Voltage output / current output
Number of outputs 1
Voltage output signal 1 V … 5 V (via DIP switch)
10 V … 0 V (via DIP switch)
0 V … 5 V (via DIP switch)
0 V … 10 V (via DIP switch)
0 V … 10.5 V (can be set via software)
Max. voltage output signal approx. 12.3 V
Non-load voltage < 17.5 V
Current output signal 0 mA … 20 mA (via DIP switch)
4 mA … 20 mA (via DIP switch)
20 mA … 0 mA (via DIP switch)
20 mA … 4 mA (via DIP switch)
0 mA … 21 mA (can be set via software)
Max. current output signal 24.6 mA
Short-circuit current < 31.5 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output ≤ 600 Ω (at 20 mA)
Ripple < 20 mVPP
< 20 mVPP (at 10 kΩ)
Resolution, outputs (voltage) 1 mV
Resolution, outputs (current) 2 µA
Behavior in the event of a sensor error configurable